Description
The single channel Relay Output, D5090S is a relay module suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508:2010 Ed.2 for high risk industries. It provides isolation between input and output contacts.
Three mutually exclusive (by DIP-Switch programming) monitoring circuits are provided:
1) line input monitoring, to allow DCS/PLC line monitoring function: when enabled, the module permits a wide compatibility towards different DCS/PLC. Driving line pulse testing, executed by DCS/PLC, is permitted by a dedicated internal circuit, to prevent relay and LED flickering.
2) low voltage input monitoring: when enabled, the module reflects a high impedance state to the control unit when the driving voltage is below the specified threshold.
3) short circuit fault detection: when enabled, it allows DCS/PLC to detect short circuit fault of module.
D5090S provides two NO contacts for normally energized load and a NC contact for service purpose, in order to switch the NE load on both supply lines.
Mounting on standard DIN-Rail or on customized Termination Boards,in Safe Area / Non Hazardous Location or in Zone 2 / Class I, Division 2 or Class I, Zone 2.
Features
- Systematic capability SIL 3
• Installation in Zone 2 / Division 2.
• SIL 3 contact for NE load and contact for service purpose.
• Line input monitoring in-field DIP Switch selectable.
• Driving input voltage monitoring.
• Input/Output isolation.
• EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
• Simplified installation using standard DIN-Rail and plug-in terminal blocks or customized Termination Boards.
Supply
24 Vdc nom (21.6 to 27.6 Vdc)
Channels
1
SIL level
SIL 3
Input
24 Vdc nom (21.6 to 27.6 Vdc), reverse polarity protected. Relay coils are
internally protected with suppressor diodes.
Current consumption: 45 mA @ 24 Vdc, typical.
Power dissipation: 1.1 W @ 24 Vdc, typical.
Output
1 voltage free SPDT relay contact identified with outputs: Out 1 (NO
contact) terminals 7-11 and Service Load Out (NC contact) terminals 9-10;
1 voltage free SPST relay contact identified with output Out 2 (NO contact)
terminals 8-12. Terminals 7-11 (Out 1) and 8-12 (Out 2) are open when
relay is de-energized, closed in energized relay condition. Service load
output (not SIL) at terminals 9-10 is normally close when relay is deenergized,
open in energized relay condition.
Contact material: Ag Alloy (Cd free), gold plated.
Contact rating: 5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load).
Contact min. switching current: 1 mA.
Contact inrush current: 6 A @ 24 Vdc, 250 Vac.
DC and AC load breaking capacity: refer to Instruction Manual.
Mechanical / electrical life: 5 * 10⁶ / 3 * 10⁴ operation, typical.
Operate / release time: 55 / 30 ms, typical.
Isolation
Input / All Outs 2.5 kV; Out 1/Out 2 500V.
Environmental conditions
Operating temperature: temperature limits -40 to +70 °C.
Storage temperature: temperature limits -45 to +80 °C.
Mounting
DIN-Rail 35 mm, or on custom Term. Board.
Weight: about 125 g.
Connection: by polarized plug-in disconnect screw terminal blocks to
accommodate terminations up to 2.5 mm² (13 AWG).
Dimensions: Width 12.5 mm, Depth 123 mm, Height 120 mm.